What size boiler do I need? Combi boiler sizes and how kW is chosen
What size boiler do I need? Choose output for your home's heat loss and hot water demand: Approved Document L says systems should not be significantly oversized. Ideal Heating explains that size means kW output, not cupboard dimensions. Its estimates offer a starting point; an engineer gives a precise recommendation.
- Approved Document L says heating sizing should use a heat loss calculation and a method suited to the dwelling; systems should not be significantly oversized.
- Ideal Heating's ballpark for up to 10 radiators is 24 to 27kW for a combi, compared with 12 to 15kW for a system or heat only boiler.
- On Ideal Heating's Logic+ Combi C24, C30 and C35, maximum heating output is 24.2kW at mean 70°C, despite different hot water outputs.
- Worcester Bosch says a higher boiler rating cannot increase hot water flow beyond the incoming mains supply.
- Padly's model pages list separate output options, shown below and checked on 27 November 2026; your installer recommends the size for your home.
Compare new boilers while you plan your replacement.
What boiler size means in kW
Ideal Heating distinguishes between power input, the energy going into the boiler, and power output, the usable heat it delivers. For sizing, the output figure is the one to discuss with your installer. Physical height, width and depth are a separate matter from the kW rating.
On Ideal Heating's Logic+ Combi specification, central heating and hot water have separate output figures. Before comparing models, ask which figure the proposed size refers to. Keeping the two figures separate helps you talk about the radiators and hot taps without treating their outputs as interchangeable.
Combi boiler sizes: separate hot water from heating
A combi deals with tap water as it is drawn, without a storage cylinder, as Worcester Bosch explains. The Padly combi boiler guide covers the layout; here, the question is how much output each job needs.
Ideal Heating explains why combis need more power: they heat hot water instantly. That puts the water you draw from the taps at the centre of this part of the sizing conversation. Its Logic+ Combi specification shows how hot water output and flow change across three sizes:
| Size | Max hot water output | Hot water flow at 35°C rise |
|---|---|---|
| C24 | 24.2kW | 9.9 l/min |
| C30 | 30.3kW | 12.4 l/min |
| C35 | 35.3kW | 14.5 l/min |
According to Ideal Heating, maximum central heating output is 24.2kW on all three at mean 70°C. Moving up this particular range therefore increases the specified hot water output, without adding maximum radiator heating output at that condition.
Vaillant lists hot water flows of 10.4, 12.2 and 14.1 litres per minute at a 35°C temperature rise for its ecoFIT pure 825, 830 and 835 respectively, showing increasing hot water delivery across another maker's combi sizes.
The makers’ rough starting points
Ideal Heating describes its radiator figures as ballpark estimates: 24 to 27kW for up to 10 radiators, 28 to 34kW for 10 to 15, and 32 to 40kW for 15 to 20. If you've counted the radiators around your home, take that count to the installer as a starting point for the conversation.
Vaillant calls its combi figures general guidelines and recommends a professional heating engineer's advice: 24 to 27kW for 1 to 2 bedrooms, 0 to 10 radiators and one bathroom; 28 to 34kW for 3 to 4 bedrooms, 10 or more radiators and 2 to 3 bathrooms; and 23 to 43kW for more than 4 bedrooms, 20 or more radiators and more than 3 bathrooms. Each group combines all those details, so keep the full description together when discussing it with your installer.
For the home-specific heating assessment, Approved Document L says the specification should use a heat loss calculation and a sizing method that accounts for the dwelling's properties. Ask your installer to explain that assessment alongside any rough estimate you've brought along, with a separate explanation of the hot water choice.
System and regular boiler sizes
Ideal Heating explains that system and heat only boilers heat stored water more slowly, by circulating hot water around a cylinder. The system boiler guide and regular boiler guide explain those arrangements.
Ideal Heating's ballpark for system or heat only boilers is 12 to 15kW for up to 10 radiators, 18 to 24kW for 10 to 15, and 30 to 40kW for 15 to 20. These are the maker's estimates for cylinder-based systems, rather than its combi estimates.
Vaillant gives system and regular boiler ranges of 9 to 18kW, 18 to 26kW and 27 to 40kW for the same household groups used in its combi guidance. The smallest group has 1 to 2 bedrooms, 0 to 10 radiators and one bathroom; the largest has more than 4 bedrooms, 20 or more radiators and more than 3 bathrooms.
In Vaillant's middle system and regular boiler group, the 18 to 26kW range accompanies 3 to 4 bedrooms, 10 or more radiators and 2 to 3 bathrooms. These are general guidelines too, with a professional heating engineer's advice recommended before choosing.
Worcester Bosch identifies regular boilers as an option for homes using lots of hot water simultaneously, homes with two or more bathrooms, and areas with low water pressure. If those details sound familiar, include the stored-water option in your discussion with the installer.
What changes the output your home needs?
Baths, showers and overlapping use
Ideal Heating's combi guide includes the number of baths and showers among its sizing factors. Describe the busiest overlap to your installer, such as a shower running while someone uses the kitchen hot tap.
Approved Document L says the hot water system should be sized for anticipated demand. For that discussion, think about the outlets you expect to use together, rather than just giving a total number of bathrooms and leaving the installer to guess how you use them.
Incoming water and achievable flow
Worcester Bosch defines a combi's flow rate as litres of hot water delivered per minute. Delivery depends on the amount and pressure of incoming mains water, together with the boiler's ability to heat it; a larger kW figure alone does not settle what will come out of the tap.
Worcester Bosch's example is a supply of 10 litres per minute: a boiler rated to deliver 14 litres per minute still cannot provide more than the incoming 10. Ask the installer to check the supply against the proposed model's hot water specification before choosing a larger version for the shower.
For the ecoFIT pure 825, 830 and 835, Vaillant specifies 2 bar as the lowest water pressure for maximum flow rate. Ask your installer to check the supply against the specification of the particular model being proposed, including the conditions attached to its quoted hot water flow.
Heat loss and the rooms themselves
Approved Document L says space heating specification should use a heat loss calculation and a sizing method that accounts for the dwelling's properties. Ask the installer to explain how the calculation reflects your home.
Ideal Heating says a Gas Safe registered engineer considers insulation quality, ceiling height and local water pressure when giving a precise recommendation. Include those details in the survey conversation, particularly if you've been looking only at radiator counts or a bedroom-based guide.
Radiators, extensions and fuel
Ideal Heating's combi guide includes property type and bedroom count among the sizing factors. Take a description of the home to your installer, including whether it's a flat, terrace or detached property, along with the number of bedrooms and radiators.
When replacing a combi as part of an extension or renovation, Ideal Heating says a larger boiler is likely to be needed, with a conservatory or en-suite among its examples. Tell the installer about any planned changes before settling on the replacement combi's output.
The fuel supply is another factor in Ideal Heating's combi guide, which names natural gas and LPG. Include the fuel you use in the details you give the installer when discussing the replacement.
Why a bigger boiler isn't automatically better
Approved Document L says heating systems should not be significantly oversized. Its separate hot water guidance carries the same advice.
Ideal Heating warns that choosing far more capacity than needed wastes money on buying and running the boiler. An underpowered boiler, it says, will leave radiators tepid and hot water in short supply. Ask the installer to explain why the proposed output fits your household's needs.
Paragraph 5.9 of Approved Document L says a gas combi should be selected to modulate down to the home's typical heating load. In plain language, it should be able to reduce its output to suit that typical demand, so the conversation needs to cover the lower end of its heating output too.
Ask how the proposed combi meets that guidance alongside its maximum hot water figure. The boiler controls guide is further reading for the controls discussion; the sizing question here is whether the chosen boiler can turn its heating output down appropriately.
What the heat loss survey should establish
Approved Document L Volume 1, 2021 edition, is guidance for England. Paragraph 5.8 says space heating specification should use both an appropriate heat loss calculation and a sizing method that accounts for the dwelling's properties. It gives the CIPHE Plumbing Engineering Services Design Guide as an example of such a method.
Hot water has its own assessment. Paragraph 5.11 says systems should be sized for anticipated domestic hot water demand, based on BS EN 12831-3 or the CIPHE guide. A radiator estimate alone therefore doesn't complete the hot water assessment described in the guidance.
Where the whole wet system is replaced, including the heating appliance, emitters and associated pipework, paragraph 5.10 says it should be sized to meet heating needs at a maximum flow temperature of 55°C or lower. If that isn't feasible, the guidance says to use the lowest possible design temperature that still meets the home's heating needs.
Ideal Heating says a Gas Safe registered engineer will provide a precise recommendation. These questions can help you talk through the proposed size with your installer:
- What heat loss calculation and sizing method support the proposed heating output?
- How have you assessed the hot water demand, including the outlets used together?
- What incoming mains flow can this combi actually use?
- Which figures on this model's specification refer to hot water and central heating?
- Can the gas combi modulate down to this home's typical heating load?
The Approved Document L publication page provides the source guidance for these sizing points.
Padly's engineers are Gas Safe registered and insured, and Padly holds its own insurance up to £10m. Once you have the sizing questions ready, Compare new boilers.
Sizes on Padly's model pages
These are the outputs listed on Padly's model pages (checked 27 November 2026), with each page's separate size options set out below. Your installer recommends the size for your home, so use the list to discuss a shortlist rather than choosing an output from the model name alone.
- Ideal Logic + Combi: 24, 30 and 35kW.
- Worcester Bosch Greenstar 1000 Combi: 25 and 30kW.
- Navien NCB300 Combi: 28, 37 and 41kW.
- Worcester Bosch Greenstar 8000 Life Combi: 30, 35, 40, 45 and 50kW.
- Ideal Logic + System: 15, 18, 24 and 30kW.
- Worcester Bosch Greenstar 4000 System: 12, 15, 18, 21 and 24kW.
- Worcester Bosch Greenstar Ri Regular: 9, 12, 15, 18, 21, 24, 27 and 30kW.
For budgeting alongside the sizing discussion, use the combi boiler prices guide, the boiler prices guide and the new boiler cost guide.
Checked on 27 November 2026. Sources: Approved Document L Volume 1, 2021 edition (gov.uk) | Ideal Heating, boiler power calculator, combi size guide and Logic+ Combi specification | Vaillant, what size boiler do I need and ecoFIT pure specification | Worcester Bosch, boilers explained | Padly boiler model pages (outputs checked 27 November 2026).
Related Padly guides
- Understanding a combi setup
- System boiler arrangements
- Regular boiler arrangements
- Combi prices for your shortlist
- Budgeting for a new boiler
- Understanding heating controls
Frequently asked questions
How much output should I consider for a three-bedroom combi?
Vaillant's general guidance is 28 to 34kW for 3 to 4 bedrooms, 10 or more radiators and 2 to 3 bathrooms. That description combines all those details, and its advice is to consult a professional heating engineer before deciding.
Is there a benefit to choosing extra boiler capacity?
Approved Document L says heating systems should not be significantly oversized. Its separate hot water guidance carries the same advice. For a gas combi, the boiler should also be selected to modulate down to the home's typical heating load, meaning it can reduce its output to suit that demand.
What does boiler size in kW mean?
Ideal Heating uses kW output rather than physical dimensions for boiler sizing. Ask your installer which specification figure describes the output being proposed, so you can discuss the size of the replacement without confusing it with the space it takes up.
How can I check a combi will cope with overlapping showers?
Worcester Bosch explains that combi flow depends on the incoming mains supply and the boiler's ability to heat the water. Ask your installer to assess the proposed model against the supply and the showers you expect to use together.
What does a heat loss calculation add to a radiator count?
Approved Document L says heating specification should use a heat loss calculation and a sizing method that accounts for the dwelling's properties. Ask your installer to explain that calculation for your home, alongside any radiator-based estimate you've used as a starting point.
Where do I start with system boiler output?
For system boilers, Ideal Heating's ballpark is 12 to 15kW for up to 10 radiators, 18 to 24kW for 10 to 15, and 30 to 40kW for 15 to 20. The maker says a Gas Safe registered engineer provides a precise recommendation.
Will moving up a combi range improve shower flow?
It depends on the incoming supply as well as the boiler. Worcester Bosch explains that a boiler capable of 14 litres per minute still only supplies 10 if that is all the mains provides. Extra output cannot overcome that supply limit.
Is my existing boiler rating a suitable replacement target?
Ideal Heating says a larger replacement combi is likely to be needed as part of an extension or renovation, including an en-suite. Before choosing the same size again, ask your installer to assess the home and the hot water use you expect after the changes.